| Model Number: |
LRD08 |
| Brand: |
Schneider Electric |
| Range: |
TeSys / TeSys Deca |
| Product Type: |
Differential Thermal Overload Relay |
| Device Short Name: |
LRD |
| Relay Application: |
Motor Protection |
| Product Compatibility: |
LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38 |
| Network Type: |
AC, DC |
| Thermal Overload Class: |
Class 10A conforming to IEC 60947-4-1 |
| Thermal Protection Adjustment Range: |
2.5-4A |
| Rated Insulation Voltage (Ui): |
600V (UL/CSA), 690V (IEC 60947-4-1) |
| Rated Operational Voltage (Ue): |
690V AC, 0-400Hz for power circuit, conforming to IEC 60947-4-1 |
| Network Frequency: |
0-400Hz |
| Mounting Support: |
Plate, Rail, Under Contactor |
| Mounting Method: |
Direct Attachment |
| Tripping Threshold: |
1.14 ±0.06 Ir conforming to IEC 60947-4-1 |
| Auxiliary Contact Composition: |
1NO + 1NC |
| Number Of Auxiliary Contacts (Normally Open): |
1 |
| Number Of Auxiliary Contacts (Normally Closed): |
1 |
| Number Of Auxiliary Contacts (Change-Over): |
0 |
| Conventional Free Air Thermal Current (Ith): |
5A for signalling circuit |
| Permissible Current: |
3A at 120V AC-15; 0.22A at 125V DC-13 (signalling circuit) |
| Associated Fuse Rating: |
4A gG; 4A BS (signalling circuit) |
| Rated Impulse Withstand Voltage (Uimp): |
6kV |
| Phase Failure Sensitivity: |
Tripping current 130% of Ir on two phases, the last one at 0 |
| Control Type: |
Red push-button (stop), Blue push-button (reset) |
| Type Of Electrical Connection (Main Circuit): |
Screw connection |
| Connections (Control Circuit): |
Screw clamp terminals, 2 cables 1-2.5mm² (flexible with/without cable end, solid without cable end) |
| Connections (Power Circuit): |
Screw clamp terminals, 1 cable 1.5-10mm² flexible without cable end / 1-4mm² flexible with cable end / 1-6mm² solid without cable end |
| Tightening Torque: |
1.7N.m (control and power circuits) |
| Temperature Compensation: |
-20°C to 60°C |
| Height: |
66mm |
| Width: |
45mm |
| Depth: |
70mm |
| Net Weight: |
0.124kg |
| Climatic Withstand: |
Conforming to IACS E10 |
| IP Degree Of Protection: |
IP20 conforming to IEC 60529 |
| Ambient Air Temperature (Operation): |
-20°C to 60°C without derating, conforming to IEC 60947-4-1 |
| Ambient Air Temperature (Storage): |
-60°C to 70°C |
| Flame Retardance: |
V1 conforming to UL94 |
| Mechanical Robustness: |
Vibrations 6Gn (IEC 60068-2-6); Shocks 15Gn for 11ms (IEC 60068-2-7) |
| Dielectric Strength: |
1.89kV at 50Hz conforming to IEC 60947-1 |
| Standards: |
EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495 |
| Product Certifications: |
IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS, ATEX INERIS, UKCA |
| Warranty: |
18 Months |
| Lifecycle Status: |
Active |