| Model Number: |
LRD22 |
| Brand: |
Schneider Electric |
| Range: |
TeSys Deca |
| Product Type: |
Differential Thermal Overload Relay |
| Relay Application: |
Motor protection |
| Product Compatibility: |
LC1D25, LC1D32, LC1D38 |
| Mounting Method: |
Direct attachment |
| Network Type: |
AC, DC |
| Thermal Overload Class: |
Class 10A conforming to IEC 60947-4-1 |
| Adjustable Current Range: |
16-24A |
| Rated Insulation Voltage (Ui): |
690V (IEC 60947-4-1); 600V (UL); 600V (CSA) |
| Rated Operational Voltage (Ue): |
690V AC, 0-400Hz conforming to IEC 60947-4-1 |
| Max. Rated Operation Voltage (Ue): |
690V |
| Network Frequency: |
0-400Hz |
| Mounting Support: |
Plate (with specific accessories), Rail (with specific accessories), Under contactor |
| Tripping Threshold: |
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Auxiliary Contact Composition: |
1NO+1NC |
| Number Of Auxiliary Contacts (Normally Open): |
1 |
| Number Of Auxiliary Contacts (Normally Closed): |
1 |
| Number Of Auxiliary Contacts (Change-Over): |
0 |
| Conventional Free Air Thermal Current (Ith): |
5A for signalling circuit |
| Permissible Current: |
1.5A at 240V AC-15; 0.1A at 250V DC-13 (signalling circuit) |
| Associated Fuse Rating: |
4A gG; 4A BS (signalling circuit) |
| Rated Impulse Withstand Voltage (Uimp): |
6kV |
| Phase Failure Sensitivity: |
Tripping current 130% of Ir on two phase, the last one at 0 |
| Control Type: |
Red push-button (stop); Blue push-button (reset) |
| Temperature Compensation: |
-20...60°C |
| Type Of Electrical Connection (Main Circuit): |
Screw connection |
| Connections - Terminals: |
Control circuit: screw clamp terminals, 1-2.5mm² (flexible/solid); Power circuit: screw clamp terminals, 1.5-10mm² (flexible/solid), 1-6mm² (flexible with cable end) |
| Tightening Torque: |
Control circuit: 1.7N.m; Power circuit: 2.5N.m |
| Height: |
66mm |
| Width: |
45mm |
| Depth: |
70mm |
| Net Weight: |
0.124kg |
| Climatic Withstand: |
Conforming to IACS E10 |
| IP Degree Of Protection: |
IP20 conforming to IEC 60529 |
| Ambient Air Temperature (Operation): |
-20...60°C without derating conforming to IEC 60947-4-1 |
| Ambient Air Temperature (Storage): |
-60...70°C |
| Flame Retardance: |
V1 conforming to UL94 |
| Mechanical Robustness: |
Vibrations 6Gn (IEC 60068-2-6); Shocks 15Gn for 11ms (IEC 60068-2-7) |
| Dielectric Strength: |
1.89kV at 50Hz conforming to IEC 60947-1 |
| Standards: |
EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495 |
| Product Certifications: |
IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS, ATEX INERIS, UKCA |
| Warranty: |