Schneider Electric LRD22: TeSys Deca Thermal Overload Relay, 16-24A adjustable thermal setting range, Class 10A, for protection of 3-phase motors rated up to 11kW@400V.

Differential Motor Protection

This thermal overload relay is a differential device that detects both phase failure and load unbalance, with a phase failure sensitivity of 130% of Ir on two phases when the third phase is at 0. The tripping threshold is set at 1.14 +/-0.06 Ir to IEC 60947-4-1, giving the thermal overload a defined, repeatable trip point for motor current protection.

Quick Diagnostics and Control

A thermal adjustment dial sets the 16-24A range, while a manual/automatic reset selector and a test selector let you simulate a trip for commissioning checks. A flag indicator shows trip status, and red stop / blue reset push buttons give direct local control. Two auxiliary contacts (1NO+1NC) carry fault signalling back to the control circuit.

Protected Settings

The thermal settings sit behind a transparent cover that can be lockable by sealing, so the adjusted overload current range stays visible but cannot be altered without breaking the seal.

Contactor and Mounting Options

This overload relay connects directly to the bottom terminals of TeSys contactors LC1D25, LC1D32 and LC1D38, forming a compact overload contactor assembly at the base of the starter. Where the relay needs to sit apart from the contactor, it can instead be fitted to DIN rail or fixed by screws using terminal block LAD7B106 (ordered separately).

Key Features of the Schneider Electric TeSys LRD22 Thermal Overload Relay Include:

  • Differential thermal overload relay for protection of 3-phase motors up to 11kW@400V
  • Adjustable thermal setting range 16-24A, Class 10A conforming to IEC 60947-4-1
  • Detects phase failure and load unbalance (phase failure sensitivity 130% of Ir on two phase, the last one at 0)
  • Tripping threshold 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
  • Manual/automatic reset selector and test selector for simulating a trip
  • Flag indicator plus red stop / blue reset push buttons for local control
  • 2 auxiliary contacts (1NO+1NC) for remote fault signalling
  • Transparent cover over the thermal settings, lockable by sealing
  • Connects directly to the bottom terminals of TeSys contactors LC1D25, LC1D32 and LC1D38
  • Also mounts on DIN rail or by screw fixing, separated from the contactor, using terminal block LAD7B106 (ordered separately)
  • Screw clamp terminal connections: control circuit 1–2.5mm², power circuit 1.5–10mm²
  • Rated operational voltage [Ue]: 690V AC, 0–400Hz
  • Rated insulation voltage [Ui]: 690V (IEC 60947-4-1), 600V (UL/CSA)
  • Rated impulse withstand voltage [Uimp]: 6kV
  • Ingress protection: IP20 conforming to IEC 60529
  • Ambient operating temperature: -20°C to 60°C without derating
  • Height: 66mm
  • Width: 45mm
  • Depth: 70mm
  • Net weight: 0.124kg
  • Certified to IEC, UL, CSA, CCC, EAC, ATEX INERIS and marine standards (BV, RINA, DNV-GL, LROS); Green Premium compliant (RoHS/REACH)
  • Warranty: 18 months
Model Number: LRD22
Brand: Schneider Electric
Range: TeSys Deca
Product Type: Differential Thermal Overload Relay
Relay Application: Motor protection
Product Compatibility: LC1D25, LC1D32, LC1D38
Mounting Method: Direct attachment
Network Type: AC, DC
Thermal Overload Class: Class 10A conforming to IEC 60947-4-1
Adjustable Current Range: 16-24A
Rated Insulation Voltage (Ui): 690V (IEC 60947-4-1); 600V (UL); 600V (CSA)
Rated Operational Voltage (Ue): 690V AC, 0-400Hz conforming to IEC 60947-4-1
Max. Rated Operation Voltage (Ue): 690V
Network Frequency: 0-400Hz
Mounting Support: Plate (with specific accessories), Rail (with specific accessories), Under contactor
Tripping Threshold: 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary Contact Composition: 1NO+1NC
Number Of Auxiliary Contacts (Normally Open): 1
Number Of Auxiliary Contacts (Normally Closed): 1
Number Of Auxiliary Contacts (Change-Over): 0
Conventional Free Air Thermal Current (Ith): 5A for signalling circuit
Permissible Current: 1.5A at 240V AC-15; 0.1A at 250V DC-13 (signalling circuit)
Associated Fuse Rating: 4A gG; 4A BS (signalling circuit)
Rated Impulse Withstand Voltage (Uimp): 6kV
Phase Failure Sensitivity: Tripping current 130% of Ir on two phase, the last one at 0
Control Type: Red push-button (stop); Blue push-button (reset)
Temperature Compensation: -20...60°C
Type Of Electrical Connection (Main Circuit): Screw connection
Connections - Terminals: Control circuit: screw clamp terminals, 1-2.5mm² (flexible/solid); Power circuit: screw clamp terminals, 1.5-10mm² (flexible/solid), 1-6mm² (flexible with cable end)
Tightening Torque: Control circuit: 1.7N.m; Power circuit: 2.5N.m
Height: 66mm
Width: 45mm
Depth: 70mm
Net Weight: 0.124kg
Climatic Withstand: Conforming to IACS E10
IP Degree Of Protection: IP20 conforming to IEC 60529
Ambient Air Temperature (Operation): -20...60°C without derating conforming to IEC 60947-4-1
Ambient Air Temperature (Storage): -60...70°C
Flame Retardance: V1 conforming to UL94
Mechanical Robustness: Vibrations 6Gn (IEC 60068-2-6); Shocks 15Gn for 11ms (IEC 60068-2-7)
Dielectric Strength: 1.89kV at 50Hz conforming to IEC 60947-1
Standards: EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495
Product Certifications: IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS, ATEX INERIS, UKCA
Warranty: 18 months