Schneider Electric TeSys Deca Thermal Overload Relay 12-18A

Product Code LRD21 TE

Available for Delivery only, change to Fast Delivery Service

£48.29

exc VAT

£57.95 : inc VAT

£57.95

inc VAT

£48.29 : exc VAT

Qty:

Schneider Electric LRD21: TeSys Deca thermal overload relay with a 12-18A adjustable setting and class 10A tripping, for protection of 3-phase motors up to 7.5kW at 400V.

Phase Failure & Load Unbalance Protection

As a differential thermal overload relay, the LRD21 detects phase failure and load unbalance, tripping at 130% of the set current on two phases when the third phase falls to zero. This gives early warning of unbalanced load conditions on the protected motor circuit.

Tamper-Evident Settings

The thermal adjustment dial sits behind a transparent cover that can be locked by sealing, so once the 12-18A setting is configured it stays protected from accidental or unauthorised changes.

Manual Controls & Remote Signalling

A manual/automatic reset selector, a test selector for simulating a trip, and dedicated reset and stop push-buttons give clear control at the relay. A flag indicator shows trip status at a glance, while the 2 auxiliary contacts (1 NO + 1 NC) carry fault signals back to a control panel.

Flexible Mounting For TeSys D Overload Contactors

The LRD21 connects directly to the bottom terminals of 3-pole TeSys D contactors LC1D18, LC1D25, LC1D32 and LC1D38, forming a compact overload relay and contactor assembly. Where the relay needs to sit apart from the contactor, it can instead be mounted on DIN rail or by screw fixing using a LAD7B106 terminal block, ordered separately.

Key Features of the Schneider Electric TeSys Deca LRD21 Thermal Overload Relay Include:

  • Differential Thermal Overload Relay With Phase Failure And Load Unbalance Detection
  • Thermal Setting Range 12 To 18A, Class 10A Tripping Conforming To IEC 60947-4-1
  • For Protection Of 3-Phase Motors Up To 7.5kW At 400V
  • Thermal Adjustment Dial, Manual/Automatic Reset Selector And Test Selector For Simulating A Trip
  • Red Stop And Blue Reset Push-Buttons With Flag Indicator For Quick Fault Identification
  • 2 Auxiliary Contacts (1 NO + 1 NC) For Remote Fault Signalling
  • Settings Protected By A Transparent Cover, Lockable By Sealing
  • Screw Clamp Terminal Connections; Connects Directly To The Bottom Terminals Of 3-Pole Contactors LC1D18 To LC1D38
  • Also Mountable On DIN Rail Or By Screw Fixing, Separate From The Contactor, Using Terminal Block LAD7B106 (Ordered Separately)
  • Rated Operational Voltage (Ue): 690V AC
  • Rated Impulse Withstand Voltage (Uimp): 6kV
  • IP20 Degree Of Protection (IEC 60529)
  • Ambient Air Temperature For Operation: -20°C To 60°C
  • Height: 66mm
  • Width: 45mm
  • Depth: 70mm
  • Net Weight: 0.124kg
  • Certified To IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS, ATEX INERIS And UKCA; Green Premium Compliant (RoHS/REACH)
  • 18 Month Warranty
Model Number: LRD21
Brand: Schneider Electric
Range: TeSys Deca
Product Type: Differential Thermal Overload Relay
Thermal Setting Range: 12-18A
Thermal Overload Class: Class 10A conforming to IEC 60947-4-1
Rated Operational Voltage (Ue): 690V AC, 0-400Hz, power circuit, conforming to IEC 60947-4-1
Rated Insulation Voltage (Ui): 690V power circuit (IEC 60947-4-1); 600V power circuit (UL); 600V power circuit (CSA)
Rated Impulse Withstand Voltage (Uimp): 6kV
Network Type: AC, DC
Network Frequency: 0-400Hz
Auxiliary Contact Composition: 1 NO + 1 NC
Conventional Free Air Thermal Current (Ith): 5A for signalling circuit
Permissible Current: 1.5A at 240V AC-15 for signalling circuit; 0.1A at 250V DC-13 for signalling circuit
Associated Fuse Rating: 4A gG for signalling circuit; 4A BS for signalling circuit
Tripping Threshold: 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Phase Failure Sensitivity: Tripping current 130% of Ir on two phases, the third at 0
Control Type: Red push-button: stop; Blue push-button: reset
Temperature Compensation: -20°C to 60°C
Mounting Support: Plate (with specific accessories); Rail (with specific accessories); Under contactor
Mounting Method: Direct attachment
Product Compatibility: LC1D18, LC1D25, LC1D32, LC1D38
Control Circuit Connection: Screw clamp terminals, 2 cables, 1-2.5mm² (flexible with/without cable end, or solid)
Power Circuit Connection: Screw clamp terminals, 1 cable, 1.5-10mm² flexible without cable end; 1-4mm² flexible with cable end; 1-6mm² solid
Tightening Torque (Control Circuit): 1.7N.m on screw clamp terminals
Tightening Torque (Power Circuit): 2.5N.m on screw clamp terminals
Height: 66mm
Width: 45mm
Depth: 70mm
Net Weight: 0.124kg
IP Degree Of Protection: IP20 conforming to IEC 60529
Ambient Air Temperature For Operation: -20°C to 60°C without derating, conforming to IEC 60947-4-1
Ambient Air Temperature For Storage: -60°C to 70°C
Flame Retardance: V1 conforming to UL 94
Mechanical Robustness: Vibrations: 6Gn conforming to IEC 60068-2-6; Shocks: 15Gn for 11ms conforming to IEC 60068-2-7
Dielectric Strength: 1.89kV at 50Hz conforming to IEC 60947-1
Climatic Withstand: Conforming to IACS E10
Standards: EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495
Product Certifications: IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS (Lloyds Register of Shipping), ATEX INERIS, UKCA
Warranty: 18 months