| Model Number: |
LRD21 |
| Brand: |
Schneider Electric |
| Range: |
TeSys Deca |
| Product Type: |
Differential Thermal Overload Relay |
| Thermal Setting Range: |
12-18A |
| Thermal Overload Class: |
Class 10A conforming to IEC 60947-4-1 |
| Rated Operational Voltage (Ue): |
690V AC, 0-400Hz, power circuit, conforming to IEC 60947-4-1 |
| Rated Insulation Voltage (Ui): |
690V power circuit (IEC 60947-4-1); 600V power circuit (UL); 600V power circuit (CSA) |
| Rated Impulse Withstand Voltage (Uimp): |
6kV |
| Network Type: |
AC, DC |
| Network Frequency: |
0-400Hz |
| Auxiliary Contact Composition: |
1 NO + 1 NC |
| Conventional Free Air Thermal Current (Ith): |
5A for signalling circuit |
| Permissible Current: |
1.5A at 240V AC-15 for signalling circuit; 0.1A at 250V DC-13 for signalling circuit |
| Associated Fuse Rating: |
4A gG for signalling circuit; 4A BS for signalling circuit |
| Tripping Threshold: |
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Phase Failure Sensitivity: |
Tripping current 130% of Ir on two phases, the third at 0 |
| Control Type: |
Red push-button: stop; Blue push-button: reset |
| Temperature Compensation: |
-20°C to 60°C |
| Mounting Support: |
Plate (with specific accessories); Rail (with specific accessories); Under contactor |
| Mounting Method: |
Direct attachment |
| Product Compatibility: |
LC1D18, LC1D25, LC1D32, LC1D38 |
| Control Circuit Connection: |
Screw clamp terminals, 2 cables, 1-2.5mm² (flexible with/without cable end, or solid) |
| Power Circuit Connection: |
Screw clamp terminals, 1 cable, 1.5-10mm² flexible without cable end; 1-4mm² flexible with cable end; 1-6mm² solid |
| Tightening Torque (Control Circuit): |
1.7N.m on screw clamp terminals |
| Tightening Torque (Power Circuit): |
2.5N.m on screw clamp terminals |
| Height: |
66mm |
| Width: |
45mm |
| Depth: |
70mm |
| Net Weight: |
0.124kg |
| IP Degree Of Protection: |
IP20 conforming to IEC 60529 |
| Ambient Air Temperature For Operation: |
-20°C to 60°C without derating, conforming to IEC 60947-4-1 |
| Ambient Air Temperature For Storage: |
-60°C to 70°C |
| Flame Retardance: |
V1 conforming to UL 94 |
| Mechanical Robustness: |
Vibrations: 6Gn conforming to IEC 60068-2-6; Shocks: 15Gn for 11ms conforming to IEC 60068-2-7 |
| Dielectric Strength: |
1.89kV at 50Hz conforming to IEC 60947-1 |
| Climatic Withstand: |
Conforming to IACS E10 |
| Standards: |
EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4, GB/T 14048.5, EN 50495 |
| Product Certifications: |
IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS (Lloyds Register of Shipping), ATEX INERIS, UKCA |
| Warranty: |
18 months |