Schneider Electric LADN40: TeSys Deca 4NO Auxiliary Contact Block with front clip-on mounting and screw clamp terminals, rated up to 690V AC.
Front Clip-On Mounting
This auxiliary contact block fits by front clip-on mounting and is compatible with TeSys D CAD, TeSys D LC1D, TeSys F LC1F, TeSys F CR1F, TeSys Deca CAD and TeSys Deca LC1D contactors and control relays. The 4NO (normally open) instantaneous contact arrangement adds extra switching points to the base device.
Rated Switching Performance
Rated operational voltage is 690V AC (25...400Hz), with operational currents of 6A at 120V AC-15, 1.04A at 690V AC-15, 0.55A at 125V DC-13 and 0.1A at 600V DC-13. A conventional free air thermal current (Ith) of 10A at 60°C and a mechanical durability rating of 30 million cycles are stated for this block, as is an insulation resistance above 10 MOhm.
Screw Clamp Termination
Connection is by screw clamp terminals, accepting 1 or 2 cables from 1mm² to 4mm², flexible or rigid, with or without cable end, tightened to 1.7N.m. This auxiliary contact block carries an IP2X degree of protection and is rated for ambient operation from -5°C to 60°C.
Multi-Standard Certification
This auxiliary contact schneider block is certified to EN/IEC 60947-5-1, GB/T 14048.5, EN 50012, UL 60947-5-1 and CSA C22.2 No 60947-5-1, with product certifications covering CB Scheme, UL, CSA, CCC, EAC and UKCA.
Key Features of the Schneider Electric TeSys Deca LADN40 Auxiliary Contact Block Include:
- 4NO (Normally Open) Instantaneous Auxiliary Contacts
- Clip-On Front Mounting; Compatible With TeSys D CAD, D LC1D, F LC1F, F CR1F, Deca CAD And Deca LC1D
- Rated Operational Voltage: 690V AC (25...400Hz)
- Rated Operational Current: 6A At 120V AC-15; 1.04A At 690V AC-15; 0.55A At 125V DC-13; 0.1A At 600V DC-13
- Rated Operation Current Ie At AC-15, 230V: 10A
- Conventional Free Air Thermal Current (Ith): 10A At 60°C
- Mechanical Durability: 30 Million Cycles
- Minimum Switching Current: 5mA; Minimum Switching Voltage: 17V
- Insulation Resistance: >10 MOhm
- Ingress Protection: IP2X (IEC 60529)
- Screw Clamp Terminals, 1–4mm² Flexible Or Rigid Cable, 1 Or 2 Cables, With Or Without Cable End
- Tightening Torque: 1.7N.m
- Height: 48mm
- Width: 44mm
- Depth: 42mm
- Weight: 0.05kg
- Colour: Dark Grey
- Operating Temperature: -5°C To 60°C; Storage Temperature: -60°C To 80°C
- Operating Altitude: Up To 3000m
- Standards: EN/IEC 60947-5-1, GB/T 14048.5, EN 50012, UL 60947-5-1, CSA C22.2 No 60947-5-1, IEC 60335-1:Clause 30.2, IEC 60335-2-40:Annex JJ, UL 60335-2-40:Annex JJ
- Product Certifications: CB Scheme, UL, CSA, CCC, EAC, UKCA
- Warranty: 18 Months