Schneider Electric LADN04: TeSys Deca Auxiliary Contact Block with 4 NC contacts, rated 690V AC, for front mounting on TeSys D, TeSys F and TeSys Deca contactors and control relays.
Reliable Switching Over Time
The LADN04 is rated for 30 million mechanical cycles, giving it a long operating life in control circuits that switch frequently. Contact operation is instantaneous, with a non-overlap time of 1.5ms on both energisation and de-energisation between NC and NO contacts, so switching transitions are clearly defined.
Flexible Termination
Screw clamp terminals accept both flexible and rigid cable from 1mm² up to 4mm², with or without cable ends, tightened to 1.7N.m. This lets installers wire the block with the cable type already specified for the panel, using a flat, Phillips No.2 or pozidriv No.2 screwdriver.
Multi-Standard Certification
The block is built to EN/IEC 60947-5-1, GB/T 14048.5, EN 50012, UL 60947-5-1 and CSA C22.2 No 60947-5-1, and carries CB Scheme, UL, CSA, CCC, EAC and UKCA certification. This supports specification on projects where multiple approval marks are required.
Clip-on front mounting fits the block directly to compatible TeSys D (LC1D), TeSys D (CAD), TeSys F (LC1F), TeSys F (CR1F) and TeSys Deca (CAD, LC1D) contactors and control relays.
Key Features of the Schneider Electric TeSys Deca LADN04 Auxiliary Contact Block Include:
- 4 NC (normally closed) instantaneous auxiliary contacts
- Clip-on front mounting for TeSys D, TeSys F and TeSys Deca contactors and control relays
- Rated operational voltage (Ue): 690V AC, 25...400Hz
- Rated operational current (Ie): 6A at 120V AC-15; 1.04A at 690V AC-15; 0.55A at 125V DC-13; 0.1A at 600V DC-13
- Rated operating current (Ie) at AC-15, 230V: 10A
- Rated insulation voltage (Ui): 690V (IEC 60947-5-1); 600V (UL); 600V (CSA)
- Conventional free air thermal current (Ith): 10A at 60°C
- Irms rated making capacity: 140A AC; 250A DC
- Permissible short-time rating: 100A for 1s; 120A for 500ms; 140A for 100ms
- Mechanical durability: 30 million cycles
- Minimum switching current: 5mA; minimum switching voltage: 17V
- Non-overlap time: 1.5ms on energisation and de-energisation
- Insulation resistance: >10 MOhm
- Screw clamp terminals accept 1 to 4mm² flexible or rigid cable, with or without cable end; tightening torque 1.7N.m
- Ingress protection: IP20 (IEC 60529); operating temperature -5°C to 60°C; storage temperature -60°C to 80°C
- Operating altitude up to 3000m
- Compliant with EN/IEC 60947-5-1, GB/T 14048.5, EN 50012, UL 60947-5-1, CSA C22.2 No 60947-5-1, IEC 60335-1 Clause 30.2, IEC 60335-2-40 Annex JJ, UL 60335-2-40 Annex JJ
- Certified to CB Scheme, UL, CSA, CCC, EAC and UKCA
- Height: 48mm
- Width: 44mm
- Depth: 42mm
- Weight: 0.05kg
- Colour: Dark grey
- Warranty: 18 months