| Model Number: |
GV2ME06 |
| Brand: |
Schneider Electric |
| Range: |
TeSys Deca |
| Product Type: |
Motor Protection Circuit Breaker |
| Device Application: |
Motor protection |
| Trip Unit Technology: |
Thermal-magnetic |
| Number Of Poles: |
3 (3P) |
| Network Type: |
AC |
| Network Frequency: |
50/60Hz |
| Utilisation Category: |
Category A conforming to IEC 60947-2; AC-3 and AC-3e conforming to IEC 60947-4-1 |
| Rated Permanent Current (Iu): |
1.6A |
| Rated Current (In): |
1.6A |
| Thermal Protection Adjustment Range: |
1...1.6A conforming to IEC 60947-2 |
| Overload Release Current Setting: |
1A |
| Magnetic Tripping Current: |
26.2A |
| Adjustment Range Undelayed Short-Circuit Release: |
22.5A |
| Conventional Free Air Thermal Current (Ith): |
1.6A conforming to IEC 60947-2 |
| Rated Operating Voltage: |
230V |
| Rated Operational Voltage (Ue): |
690V AC 50/60Hz conforming to IEC 60947-2 |
| Rated Insulation Voltage (Ui): |
690V AC 50/60Hz conforming to IEC 60947-2 |
| Rated Impulse Withstand Voltage (Uimp): |
6kV conforming to IEC 60947-2 |
| Motor Power: |
0.37kW at 400/415V AC; 0.55kW at 400/415V AC; 0.37kW at 500V AC; 0.55kW at 500V AC; 0.75kW at 500V AC; 0.75kW at 690V AC; 1.1kW at 690V AC |
| Rated Operation Power At AC-3, 400V: |
0.55kW |
| Rated Operation Power At AC-3, 230V: |
0.25kW |
| Rated Short-Circuit Breaking Capacity (Icu) At 400V, AC: |
100kA |
| Breaking Capacity (Icu): |
100kA at 230/240V, 400/415V, 440V, 500V and 690V AC, conforming to IEC 60947-2 |
| Rated Service Short-Circuit Breaking Capacity (Ics): |
100% at 230/240V, 400/415V, 440V, 500V and 690V AC, conforming to IEC 60947-2 |
| Phase Failure Sensitivity: |
Yes, conforming to IEC 60947-4-1 |
| Suitability For Isolation: |
Yes, conforming to IEC 60947-1 |
| Power Dissipation Per Pole: |
2.5W |
| Mechanical Durability: |
100000 cycles |
| Electrical Durability: |
100000 cycles for AC-3 at 415V (In); 100000 cycles for AC-3e at 415V (In) |
| Rated Duty: |
Uninterrupted, conforming to IEC 60947-4-1 |
| Type Of Control Element: |
Push button |
| Switch Off Technique: |
Thermomagnetic |
| Type Of Electrical Connection Of Main Circuit: |
Screw connection |
| Connections - Terminals: |
Power circuit screw clamp terminal, 2 cables: 1...6mm² solid; 1.5...6mm² flexible without cable end; 1...4mm² flexible with cable end |
| Tightening Torque: |
1.7N.m on screw clamp terminal |
| Fixing Mode: |
35mm symmetrical DIN rail (clipped); panel (screwed, with adaptor plate) |
| Mounting Position: |
Horizontal; Vertical |
| Device Construction: |
Complete device in housing |
| Colour: |
Dark grey |
| Width: |
45mm |
| Height: |
89mm |
| Depth: |
78.2mm |
| Net Weight: |
0.26kg |
| Degree Of Protection (IP Rating): |
IP20 conforming to IEC 60529 |
| IK Degree Of Protection: |
IK04 |
| Climatic Withstand: |
Conforming to IACS E10 |
| Ambient Air Temperature For Operation: |
-20°C...60°C |
| Ambient Air Temperature For Storage: |
-40°C...80°C |
| Fire Resistance: |
960°C conforming to IEC 60695-2-11 |
| Mechanical Robustness: |
Shocks: 30Gn for 11ms; Vibrations: 5Gn, 5...150Hz |
| Operating Altitude: |
<= 2000m |
| Standards: |
EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40 Annex JJ; IEC/EN 60335-1 Clause 30.2 |
| Product Certifications: |
CB Scheme; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds Register Of Shipping); BV; RINA; DNV-GL |
| Environmental Compliance: |
Green Premium compliant (RoHS, REACh) |
| Warranty: |
18 months |