Schneider Electric A9D56806: Acti9 iC60H plug-on neutral RCBO, 1P+Ns, 6A Type B curve, 30mA Type A earth-leakage sensitivity, 10000A rated breaking capacity.

Safety & Reliability

As an earth leakage circuit breaker RCBO, this device combines overcurrent and earth-leakage protection in a single module. Its Type A sensitivity of 30mA, with instantaneous time delay, is rated for AC and pulsating DC residual currents. The Icn rated short-circuit breaking capacity reaches 10000A to IEC 61009-2-2, with an Ics rated service breaking capacity of 7500A. Class II electrical insulation and a 4kV rated impulse withstand voltage support reliable operation on TN earthing systems.

Visitrip & Visisafe Fault Indication

The Visitrip indicator shows which circuit has tripped, reducing the time spent identifying a fault on site. The Visisafe green strip confirms the contacts have physically opened, giving a clear visual check before downstream maintenance work begins.

Plug-On Neutral Installation

This Acti9 iC60H RCBO is designed for plug-on neutral mounting onto Isobar A and Isobar B distribution boards within the Acti9 Isobar P system, connecting directly onto the busbar rather than requiring separate neutral wiring. The manufacturer's instructions specify it must not be used as an incomer device and is not compatible with earlier Acti9 ISOBAR systems.

Durability & Terminal Capacity

Rated for 20000 mechanical cycles and 5000 electrical cycles, the device accepts screw clamp terminal connections of up to 25mm² rigid conductor at the top and 16mm² rigid conductor at the bottom, with a padlock option available to lock the device in the on or off position.

Key Features of the Schneider Electric Acti9 iC60H A9D56806 RCBO Include:

  • Combined overcurrent and 30mA Type A earth-leakage protection in a single RCBO module
  • Visitrip fault indicator shows the faulty circuit to help reduce intervention time
  • Visisafe green strip confirms physical contact opening ahead of downstream maintenance
  • Plug-on neutral design for Isobar A and Isobar B distribution boards
  • Rated Current (In): 6A at 50°C
  • Tripping Characteristic: Type B curve, Undelayed disconnection
  • Earth-Leakage Sensitivity: 30mA, Type A, Instantaneous time delay
  • Rated Short-Circuit Breaking Capacity (Icn): 10000A to IEC 61009-2-2
  • Rated Service Breaking Capacity (Ics): 7500A
  • Rated Operational Voltage (Ue): 230/240V AC 50/60Hz
  • Rated Insulation Voltage (Ui): 400V AC; Rated Impulse Withstand Voltage (Uimp): 4kV
  • Poles: 1P+Ns
  • Mechanical Durability: 20000 Cycles; Electrical Durability: 5000 Cycles
  • Ingress Protection: IP20 (IP40 in modular enclosure)
  • Height: 110mm
  • Width: 18mm
  • Depth: 72mm
  • Weight: 156g
  • Colour: White
  • Compliance: BS EN 61009-1, IEC 61009-1, IEC 61009-2-2; CB certified
  • Warranty: 18 Months
Model Number: A9D56806
Brand: Schneider Electric
Range: Acti9 Isobar P iC60H RCBO's
Product Type: Residual Current Breaker With Overcurrent Protection (RCBO)
Poles: 1P+Ns
Number Of Protected Poles: 1
Number Of Poles (Total): 2
Rated Current (In): 6A At 50°C
Rated Voltage: 240V
Rated Operational Voltage (Ue): 230/240V AC 50/60Hz
Tripping Characteristic: Type B
Disconnection Characteristic: Undelayed
Earthing System: TN
Earth-Leakage Sensitivity: 30mA
Earth-Leakage Protection Class: Type A
Earth-Leakage Protection Time Delay: Instantaneous
Residual Current Tripping Technology: Voltage Dependent
Rated Short-Circuit Breaking Capacity (Icn): 10000A At 240V AC (IEC 61009-2-2)
Rated Service Breaking Capacity (Ics): 7500A At 240V AC (IEC 61009-2-2)
Rated Insulation Voltage (Ui): 400V AC 50/60Hz
Rated Impulse Withstand Voltage (Uimp): 4kV
Surge Current: 250A
Trip Unit Technology: Thermal-Magnetic
Magnetic Tripping Limit: 3...5 x In
Electrical Insulation Class: Class II
Current Limiting Class: 3
Over Voltage Category: II
Pollution Degree: 3
Suitability For Isolation: Yes
Mounting Mode: Plug-On
Mounting Support: Isobar A, Isobar B
Neutral Position: Left
Network Frequency: 50/60Hz
Network Type: AC
Contact Position Indicator: Yes
Control Type: Toggle
Local Signalling: ON/OFF Indication, Fault Indication
Comb Busbar And Distribution Block Compatibility: No
Width In Number Of Modular Spacings (9mm Pitches): 2
Height: 110mm
Width: 18mm
Depth: 72mm
Net Weight: 156g
Colour: White
Mechanical Durability: 20000 Cycles
Electrical Durability: 5000 Cycles
Locking Options: Padlock In On Or Off Position
Connections - Terminals: Screw Clamp Terminal (Top) 1-16mm² Flexible, (Bottom) 1-10mm² Flexible, (Top) 1-25mm² Rigid, (Bottom) 1-16mm² Rigid, Plug-On Neutral (Upstream)
Connectable Conductor Cross Section (Solid-Core): 1mm²
Connectable Conductor Cross Section (Multi-Wired): 1mm²
Wire Stripping Length: 14mm (Top), 13mm (Bottom)
Tightening Torque: 3.5N.m (Top), 2N.m (Bottom)
Earth-Leakage Protection: Integrated
Standards: BS EN 61009-1, IEC 61009-1, IEC 61009-2-2
Product Certifications: CB
IP Degree Of Protection: IP20 (IEC 60529), IP40 (Modular Enclosure, IEC 60529)
Ambient Air Temperature For Operation: -15 To 60°C
Ambient Air Temperature For Storage: -40 To 85°C
Relative Humidity: 95% At 55°C
Warranty: 18 Months

Recommended Products