Schneider Electric A9TDFD620: Acti9 Active iCV40H ARC 20A Active Arc Fault Detection RCBO, 1P+N, C curve, 30mA Type A-SI, with EcoStruxure Panel Server compatibility.

Active Arc Fault Protection

This Acti9 Active iCV40 ARC device combines arc fault detection with standard RCBO protection. It guards against short circuit, cable overload, electrical shock by indirect contact and fire hazards, with Type A-SI (Super Immunised) earth leakage protection at 30mA sensitivity and instantaneous trip delay.

Faster Fault Diagnosis

Two VisiTrip indicators show the faulty circuit and identify the type of fault quickly, reducing the time needed to locate and resolve an intervention. Local signalling covers ON, OFF and fault trip states, supported by an LED arc fault diagnostic indicator.

Connected Monitoring

The device communicates with EcoStruxure Panel Server Entry, Universal and Advanced gateways. Its pre-alarming system can flag overload, earth leakage and overvoltage events, and it measures voltage, current, active power and power factor for ongoing circuit visibility.

Durability & Installation

Limitation class 3 (to EN/IEC 60898-1) improves downstream circuit protection cost. The device is rated for 20000 mechanical and 20000 electrical durability cycles at 230V AC 50Hz, and clips onto DIN rail across 4 x 9mm pitches with top and bottom cable entry.

Key Features of the Schneider Electric Acti9 Active iCV40 ARC A9TDFD620 Include:

  • Active arc fault detection protects against short circuit, cable overload, electrical shock by indirect contact and fire hazard
  • Two VisiTrip indicators show the faulty circuit and identify the fault type to speed up diagnosis
  • Compatible with EcoStruxure Panel Server Entry, Universal and Advanced concentrators
  • Pre-alarming for overload, earth leakage and overvoltage; measures voltage, current, active power and power factor
  • 1P+N configuration, 1 protected pole, 20A rated current, C tripping curve
  • Type A-SI (Super Immunised) earth-leakage protection, 30mA sensitivity, instantaneous time delay
  • Breaking capacity 10000A Icn at 230V AC (EN/IEC 61009-2-1); 10kA Icu at 230V AC (EN/IEC 60947-2)
  • Limitation class 3 (EN/IEC 60898-1) improves downstream circuit protection cost
  • Suitable for isolation with padlocking device for lock-out
  • Toggle control with ON, OFF and fault trip local signalling plus LED arc fault diagnostic
  • Clip-on DIN rail mounting, 4 x 9mm pitches, top and bottom cable entry
  • Mechanical durability 20000 cycles; electrical durability 20000 cycles at 230V AC 50Hz
  • Colour: White (RAL 9003)
  • Height: 91mm
  • Width: 36mm
  • Depth: 73mm
  • Net weight: 220g
  • Compliant with EN/IEC 62606, EN/IEC 61009-1, EN/IEC 60947-2, EN/IEC 61009-2-1 and BS EN 62606; UKCA certified
  • Warranty: 18 months
Model Number: A9TDFD620
Brand: Schneider Electric
Range: Acti9
Product Type: Active Arc Fault Detection RCBO
Product Name: Acti9 Active iCV40 ARC
Device Short Name: iCV40H ARC
Product Specific Application: Arc Fault Detection
Standards: EN/IEC 62606; EN/IEC 61009-1; EN/IEC 60947-2; EN/IEC 61009-2-1; BS EN 62606
Poles Description: 1P + N
Number Of Protected Poles: 1
Curve Code: C
Breaking Capacity Code: H
Breaking Capacity: 10000A Icn at 230V AC 50Hz conforming to EN/IEC 61009-2-1; 10kA Icu at 230V AC 50Hz conforming to EN/IEC 60947-2
Rated Breaking And Making Capacity: Idm 3000A at 230V AC 50Hz conforming to EN/IEC 61009-2-1
Neutral Position: Left
Network Type: AC
Earth-Leakage Protection Time Delay: Instantaneous
Earth-Leakage Protection Class: Type A-SI (Super Immunised)
Electrical Data Recording: Date and time; Maintenance indicators
Concentrator Compatibility: EcoStruxure Panel Server Advanced; EcoStruxure Panel Server Entry; EcoStruxure Panel Server Universal
Event Management: Overvoltage; Earth leakage; Overload
Type Of Measurement: Voltage; Active power; Current; Power factor
Accuracy: Voltage: +/- 2%; Current: +/- 2%; Power: +/- 5%
Suitability For Isolation: Yes
Residual Current Tripping Technology: Voltage independent
Trip Unit Technology: Thermal-magnetic
Earth-Leakage Protection: Integrated
In Rated Current: 20A
Network Frequency: 50Hz
Ue Rated Operational Voltage: 230V AC 50Hz
Device Location In System: Outgoer
Magnetic Tripping Limit: 5...10 x In
Ics Rated Service Breaking Capacity: 7500A AC 50Hz conforming to EN/IEC 61009-2-1; 7.5kA AC 50Hz conforming to EN/IEC 60947-2
Limitation Class: 3
Ui Rated Insulation Voltage: 250V AC 50Hz between phase and neutral
Threshold Tripping Voltage: 275V for +/- 5V
Uimp Rated Impulse Withstand Voltage: 4kV
Contact Position Indicator: Yes
Control Type: Toggle
Local Signalling: ON, OFF, fault trip; LED arc fault diagnostic
Mounting Mode: Clip-on
Mounting Support: DIN rail
Colour: White (RAL 9003)
Mechanical Durability: 20000 cycles
Electrical Durability: 20000 cycles 230V AC 50Hz
Overvoltage Category: III
Locking Options Description: Padlocking device
Cable Entry: Top and bottom
Connections - Terminals: Tunnel type terminal 1...16mm² rigid; Tunnel type terminal 1...10mm² flexible
Wire Stripping Length: 14mm
Tightening Torque: 2N.m
Comb Busbar And Distribution Block Compatibility: YES
9mm Pitches: 4
Height: 91mm
Width: 36mm
Depth: 73mm
Net Weight: 220g
Total Power Losses: 4.068W
Power Losses Per Pole: 2.8W
Power Losses On Neutral: 1.272W
Earth-Leakage Sensitivity: 30mA
IP Degree Of Protection: IP20 conforming to IEC 60529
Pollution Degree: 2 conforming to EN/IEC 62606
Tropicalisation: Severity B conforming to IEC 60068-2-30 for 28 days
Relative Humidity: 95% at 55°C
Operating Altitude: 2000m
Ambient Air Temperature For Operation: -25...50°C
Ambient Air Temperature For Storage: -40...80°C
Product Certifications: UKCA