Schneider Electric Acti9 Active Arc Fault Detection RCBO

Product Code A9TDFD632 MG

Available for Delivery only, change to Fast Delivery Service

£218.85

exc VAT

£262.62 : inc VAT

£262.62

inc VAT

£218.85 : exc VAT

Qty:

Schneider Electric A9TDFD632: Acti9 Active iCV40 ARC, 1P+N 32A C curve arc fault detection RCBO with 30mA Type A-SI earth-leakage protection and 10000A breaking capacity.

Early Arc Fault Detection and Diagnostics

The iCV40H ARC combines LED arc fault diagnostics with VisiTrip indicators, showing which fault type has been detected (short-circuit, overload, earth leakage or arc fault) so the affected circuit is identified quickly. Local signalling shows ON, OFF or fault trip status, and a contact position indicator confirms the true state of the contacts.

Connected Monitoring With EcoStruxure

This RCBO communicates with EcoStruxure Panel Server Entry, Universal and Advanced gateways, reporting overvoltage, earth leakage and overload events alongside voltage, current, active power and power factor measurements. Electrical data recording logs date, time and maintenance indicators for the device.

Protection and Installation

Earth-leakage protection is Type A-SI (Super Immunised) with instantaneous tripping at 30mA, and the device carries a breaking capacity of 10000A Icn (10kA Icu). Limitation class 3 reduces the cost of downstream circuit protection. The unit clips onto a DIN rail, accepts a padlocking device for isolation, and is compatible with comb busbars and distribution blocks.

Key Features of the Schneider Electric Acti9 Active iCV40 ARC A9TDFD632 Include:

  • LED Arc Fault Diagnostic With VisiTrip Fault Indicators For Fast Circuit Identification
  • Local Signalling Shows On, Off And Fault Trip Status, Plus Contact Position Indicator
  • Communicates With EcoStruxure Panel Server Entry, Universal And Advanced Gateways
  • Reports Overvoltage, Earth Leakage And Overload Events; Measures Voltage, Current, Active Power And Power Factor
  • Electrical Data Recording: Date, Time And Maintenance Indicators
  • Type A-SI (Super Immunised) Earth-Leakage Protection, 30mA Sensitivity, Instantaneous Trip
  • 1P+N, 1 Protected Pole, 32A Rated Current, C Curve
  • Breaking Capacity: 10000A Icn (EN/IEC 61009-2-1); 10kA Icu (EN/IEC 60947-2)
  • Limitation Class 3 For Reduced Downstream Circuit Protection Cost
  • Clip-On DIN Rail Mounting, 4 x 9mm Pitches; Comb Busbar And Distribution Block Compatible
  • Padlocking Device For Isolation
  • IP20 Degree Of Protection (IEC 60529)
  • Height: 91mm
  • Width: 36mm
  • Depth: 73mm
  • Net Weight: 220g
  • UKCA Certified
  • Warranty: 18 Months
Model Number: A9TDFD632
Brand: Schneider Electric
Range: Acti9
Product Type: Active Arc Fault Detection RCBO
Product Name: Acti9 Active iCV40 ARC
Device Short Name: iCV40H ARC
Product Specific Application: Arc Fault Detection
Standards: EN/IEC 62606; EN/IEC 61009-1; EN/IEC 60947-2; EN/IEC 61009-2-1; BS EN 62606
Poles Description: 1P + N
Number Of Protected Poles: 1
Curve Code: C
Breaking Capacity Code: H
Breaking Capacity: 10000A Icn at 230V AC 50Hz conforming to EN/IEC 61009-2-1; 10kA Icu at 230V AC 50Hz conforming to EN/IEC 60947-2
Rated Breaking And Making Capacity: Idm 3000A at 230V AC 50Hz conforming to EN/IEC 61009-2-1
Neutral Position: Left
Network Type: AC
Earth-Leakage Protection Time Delay: Instantaneous
Earth-Leakage Protection Class: Type A-SI (Super Immunised)
Electrical Data Recording: Date and time; Maintenance indicators
Concentrator Compatibility: EcoStruxure Panel Server Advanced; EcoStruxure Panel Server Entry; EcoStruxure Panel Server Universal
Event Management: Overvoltage; Earth leakage; Overload
Type Of Measurement: Voltage; Active power; Current; Power factor
Accuracy: Voltage: ±2%; Current: ±2%; Power: ±5%
Suitability For Isolation: Yes
Residual Current Tripping Technology: Voltage independent
Trip Unit Technology: Thermal-magnetic
Earth-Leakage Protection: Integrated
Rated Current (In): 32A
Network Frequency: 50Hz
Rated Operational Voltage (Ue): 230V AC 50Hz
Device Location In System: Outgoer
Magnetic Tripping Limit: 5...10 x In
Rated Service Breaking Capacity (Ics): 7500A AC 50Hz conforming to EN/IEC 61009-2-1; 5kA AC 50Hz conforming to EN/IEC 60947-2
Limitation Class: 3
Rated Insulation Voltage (Ui): 250V AC 50Hz between phase and neutral
Threshold Tripping Voltage: 275V for ±5V
Rated Impulse Withstand Voltage (Uimp): 4kV
Contact Position Indicator: Yes
Control Type: Toggle
Local Signalling: ON, OFF, fault trip; LED arc fault diagnostic
Mounting Mode: Clip-on
Mounting Support: DIN rail
Colour: White (RAL 9003)
Mechanical Durability: 20000 cycles
Electrical Durability: 10000 cycles 230V AC 50Hz
Overvoltage Category: III
Locking Options Description: Padlocking device
Cable Entry: Top and bottom
Connections - Terminals: Tunnel type terminal 1-16mm² rigid; Tunnel type terminal 1-10mm² flexible
Wire Stripping Length: 14mm
Tightening Torque: 2N.m
Comb Busbar And Distribution Block Compatibility: Yes
9mm Pitches: 4
Height: 91mm
Width: 36mm
Depth: 73mm
Net Weight: 220g
Total Power Losses: 6.333W
Power Losses Per Pole: 4.48W
Power Losses On Neutral: 1.852W
Earth-Leakage Sensitivity: 30mA
IP Degree Of Protection: IP20 conforming to IEC 60529
Pollution Degree: 2 conforming to EN/IEC 62606
Tropicalisation: Severity B conforming to IEC 60068-2-30 for 28 days
Relative Humidity: 95% at 55°C
Operating Altitude: 2000m
Ambient Air Temperature For Operation: -25...50°C
Ambient Air Temperature For Storage: -40...80°C
Product Certifications: UKCA
Warranty: 18 months

Recommended Products